Does the DAS Backbone Cable Need to Be Fire-Rated?

info466216
Oct 5
4 min read

It depends on what the system is for. A DAS that serves as an emergency responder radio system is normally expected to keep working through a fire, which in the US means pathway survivability of 2 hours under NFPA 1221 for the non-sprinklered case. A private DAS that only serves the building's own staff has no such rule of its own, but the cable still has to meet the building's fire-retardant and fire-stopping requirements, and it should be specified to survive long enough to be useful. I could not find a Singapore clause that sets a numeric survivability rating for a private two-way radio DAS, so confirm the requirement with your Qualified Person and SCDF before you tender.

What is pathway survivability, and why does it matter?

Pathway survivability is the length of time the cable, enclosures and power feeds of a radio system keep carrying signal while a fire attacks them. It matters because the usual failure is not at the antenna: it is a trunk cable in a riser that burns through, taking every floor above the break with it. The floors that lose coverage first are the ones above the fire, which is where responders are heading.

What does NFPA 1221 actually require?

NFPA 1221 describes two levels. Level 2 asks for 2 hours of protection and allows three routes: listed 2-hour circuit integrity cable (mineral-insulated cable is the usual example), cable enclosed in a 2-hour fire-rated assembly, or a listed 2-hour electrical circuit protective system. Level 1 is a lesser option for fully sprinklered buildings, using metal raceway such as EMT, IMC or rigid conduit. BDA and head-end equipment is expected to sit in a 2-hour rated room or a listed rated enclosure. One source notes the requirement has been carried into NFPA 1225 in newer editions, so check which edition a given jurisdiction enforces. This is US practice and is a useful benchmark, not Singapore law.

Do standard coax and leaky feeder meet that requirement?

No. Standard 1/2 inch and 7/8 inch coax and leaky feeder with a halogen-free, low-smoke, flame-retardant jacket will not give you 2 hours at fire temperatures. The jacket helps with smoke and flame spread, which is a different property from circuit integrity. The practical options are to run the trunk in a fire-rated riser shaft, to wrap or enclose it in a listed fire-protection system, or to use fibre in a rated pathway for an active DAS. Singapore practice for fire-retardant cabling points to SS 299 for flame performance, but verify that against the current Fire Code and the project specification, because flame retardance and circuit integrity are not interchangeable.

What should you specify for a Singapore building?

Start with the intent. If the radio system is relied on by the building's emergency response, ask the QP and SCDF what survivability they will accept in writing, and design to that. If it is a private operations system, I would still specify the following as good practice:

  • Halogen-free, low-smoke, flame-retardant jackets on all riser and plenum cable, with penetrations fire-stopped to the rating of the wall or slab.

  • Vertical trunks routed in the ELV or fire-rated riser, not in open ceiling voids.

  • Head-end, BDA and battery in a separate rated room where the building allows it.

  • Backup power sized for the stated hours and an alarm path to the control room.

  • Antenna feeds on a ring or redundant branch so one cut does not black out a whole zone.

What does fire survivability cost?

Rated pathway adds cost mainly in the vertical trunk, because that is the single point of failure. The horizontal floor runs are usually left standard. Treat any numbers from US sources as indicative only and get a quote for the specific riser. See also what ongoing costs to budget after a BDA/DAS is installed.

Related questions

Is a 2-hour fire rating required for every DAS in Singapore? I found no published Singapore rule that sets one for a private two-way radio DAS. A system tied to emergency responder use may attract a requirement, so confirm with the QP and SCDF.

Is low-smoke zero-halogen cable the same as fire-rated cable? No. Low-smoke zero-halogen describes what the jacket gives off when it burns. Fire-rated or circuit integrity cable is tested to keep conducting for a set time. Both can be required.

Does fibre solve the survivability problem? Only partly. Fibre in a rated pathway resists heat better than coax, but the remote units still need power, and the power feed needs the same protection.

For how Singapore coverage requirements compare with the US approach, see COPIF versus IFC 510.

How Suneast approaches survivability

Suneast designs and installs in-building radio coverage for Singapore buildings, routing trunks through ELV risers, specifying flame-retardant low-smoke cable with fire-stopped penetrations, and documenting the backup power and alarm arrangements. Where a rated pathway is required, we design to the rating the QP and SCDF confirm and show the vertical trunk and head-end location on the proposal drawings.

Recent Posts

See All

Comments


Get in touch

with the Professionals

Contact Us

Thanks for submitting!

Get in touch with us now, to get a

professional site survey or your maintenance servicing with us.

Walkie-Talkie
Motorola

UEN: 198004679W

© 2020 by Suneast Pte Ltd. 

CONTACT

Phone: 6296 4233

Email: info@suneast.com.sg

60 Kaki Bukit Place, 

#06-04 Eunos Tech Park,

Singapore 415979

WORKING HOURS

Mon - Fri: 9am - 6pm​​

Sat, Sun: Closed

bottom of page